Skip to main content

Case Study - Packed Tower Scrubber System for NH3 and H2S Removal

 

Customer’s Problem

The off-gases originate from a large paddle dryer that processes egg waste, along with other miscellaneous equipment such as material conveyors, two vessels, and two dumpsters.

During the dehydration process, the egg waste releases odorous compounds—specifically ammonia (NH3) and hydrogen sulfide (H2S)—along with water vapor. Most of the water vapor is condensed before the remaining air streams combine and enter the scrubber system.

Inlet Gas Conditions and Required Removal Efficiency

  • Contaminants: NH3 and H2S

  • Minimum Overall Removal Efficiency: 99%

  • Desired Outlet Composition:

    • H2S: <= 1 ppm

    • NH3: <= 3 ppm

  • Normal Gas Flow Rate: 5,000 ACFM (Air, H2O, H2S, and NH3)

  • Normal Inlet Temperature: 84°F

  • Inlet Pressure: –2.0 inches H2O

Solution Provided

To address the customer’s requirements, two packed tower scrubbers were supplied. The first stage uses sulfuric acid as a chemical reagent to remove NH3, while the second stage uses caustic and bleach to remove H2S. The relevant chemical reactions are as follows:

H2SO4(aq)+2NH3→(NH4)2SO4(aq)

H2S+2NaOH(aq)+NaOCl→Na2SO4(aq)+NaCl(aq)+H2O

Both scrubbers were installed indoors as part of the egg waste system. To conserve space, two tubular fans were mounted on a single skid—one operational and one on standby. Pick-up branches from each off-gas point vent into a main trunk line that feeds the vent gas into the scrubber system.

The system is equipped with sensors for pH, ORP, conductivity, differential pressure, and pressure, as well as level switches, level detectors, leak detectors, pneumatically controlled valves, and solenoid valves. Both on/off and PID loop controls are integrated with a PLC, allowing the system to operate automatically. In the event of any abnormality, the PLC triggers an alarm and/or automatically shuts down the system.

Packed Towers installed


Results

During startup and commissioning, the NH3 and H2S concentrations in the incoming vent gas varied. However, the Continuous Emission Monitoring System (CEMS) on the exhaust duct never triggered any alarms. Outlet NH3 levels remained consistently below 3 ppm, and H2S levels below 1 ppm, meeting the desired performance targets.



Comments

Popular posts from this blog

What you have to know when applying blast gate damper

  Introduction A damper is a device that adjusts the volume of airflow passing through the outlet, inlet or duct. By proper adjustment of all dampers in a system, a desired distribution of airflows in all the branches can be obtained, while minimizing the total airflow of the system to save energy— this is also termed air balancing. The most common dampers used in industrial ventilation and dust collection systems to balance airflows are slide gate dampers (The slide gate, also called “blast gate or cut-off” damper). In a slide gate damper (see Figure 1 of a straight flat slide gate damper), the slide is inserted perpendicular to the flow. Figure 1 A sample of straight flat slide gate damper As the gate is sliding into the duct, it will add resistance to the airflow and consequently reduce the volume of airflow, while increasing airflows in all other branches. Withdrawing the gate has the reverse effect on that branch and all the others in a system. Interaction between a fan ...

Push-pull ventilation system for open surface tank saves air flow

  Three sections in this blog: Push-pull ventilation system and its advantages Disadvantages of general ventilation and side exhaust systems Methods to design a push-pull ventilation system Push-pull ventilation system and its advantages Open surface tanks used in industrial processes often need ventilating to remove harmful pollutants (vapors, fumes or aerosols) from the working environment. One method of removing pollutants is the so-called side push-pull ventilation system, in which a jet of air is blown (or pushed) from one side of the tank and collected (or pulled) by an exhaust hood on the opposite parallel side. This system is particularly useful for large tanks where access requirements preclude the use of an overhead canopy, and the size of the tank makes side (or rim) exhaust systems prohibitively expensive. Most agree that a push-pull ventilation system can yield air savings of up to 50% compared to a side suction only hood. An illustration of a push-pull system for an o...

Why and How to do Air Balancing on Industrial Ventilation and Dust Collection Systems?

  Introduction The performances of all the hoods in the whole system normally decide the success of industrial ventilation and dust collection systems from the point of a system owner’s view. The appropriate hood design and its needed airflow rate require the application of good ventilation practice, mastery of the technical knowledge and the ability and patience to do the mathematical calculations. When more than one hood is connected to one ventilation system, the design engineer has to assure that each hood can and will receive the volume of airflow equal or above its designed value and the whole system operates with the minimum possible airflow rate to save energy. This task is termed air balancing of the system or duct balancing. Unbalanced systems cause problems On the contrary, examine the case where one or more hoods are unable to receive desired volume of airflow from an unbalanced ventilation system. It is not uncommon that many hoods are receiving airflow volumes...