Skip to main content

Troubleshooting: Air Header got no air for the pulse jet cleaning system

 

One customer told us that their dust collection system had a very weak suction on the grinding process line, and we went to their workshop on-schedule to do troubleshooting. 

Introduction of the dust collection system

The dusty air from the plastic grinder first ran through a cyclone and the separated dust from the cyclone directly went back to the process; the airflow with fine particles from the cyclone went to a cartridge dust collector, and then the filtered air was released to outside of the building.

Since the plastic dust is combustible, an explosion panel and a vent duct were installed on the dust collector, and a non-return valve on the ductwork just in front of the dust collector inlet.

The cartridge dust collector was equipped with a pulse jet cleaning system controlled by a Photohelic pressure gauge. The Photohelic Gauge measures the Differential Pressure and provides the capability for “on-demand” cleaning in conjunction with a Timer Board.

Troubleshooting process

When we walked around the cartridge dust collector doing a visual inspection, we saw that the pointer of the pressure gauge on the air header pointed to 0 (zero) psi, then we tracked down the supply line of the compressed air and found that the shutoff valve on the compressed air branch line to the air header was turned off (Figure 1). Apparently, the customer forgot to turn it back on. 

Figure 1 the shutoff valve was turned off and forgotten
Before opening the shutoff valve, we used this chance to empty any condensed water in the air header. On the drainpipe of the air header, no drain valve was installed, only a blind cap. The filter and water trap bowl of the air filter and pressure regulator piggyback in front of the air header were inspected as well.

The shutoff valve was cautiously opened, and the air header pressure roared to about 83 psi (Figure 2). Then the manual drain of the piggyback was tested. 

No abnormal sounds around the air header, solenoid valve manifold, diaphragm valves, and blowpipes indicated air leaks.

 
Figure 2 air header pressure, 83 psi
After tagout/lockout, we opened the access cover and inspected the inside of the dust collector and took out cartridges for cleaning with compressed air on the floor. From the look of the cartridge body and inside of the collector, pulse jet cleaning had not functioned for some time (Figure 3&4). 

The collected dust was discharged from the hopper directly to a barrel below on the ground through a flex hose. The barrel was almost empty.

Figure 3 inside of the dust collector without pulse cleaning


Figure 4 cartridges without pulse cleaning
 The cyclone and the ductwork were also inspected to make sure they were not clogged. They were fine too.

The differential pressure hoses connected to the Photohelic pressure gauge were inspected. They were not clogged.

We manually triggered the diaphragm valves to make sure they were functioning properly. They were fine.

After the system was turned on, it ran normally.

The high set point and the low set point of the differential pressure on the Photohelic pressure gauge were lowered by hand to turn on the pulse cleaning in a shorter time; the solenoid valves were then inspected, and they all functioned properly, and then both set points were turned back to its old settings.

The integrated fan and motor were on top of the dust collector. We checked the vibration of the compact combo, and they were fine; we also checked the outlet damper, and it was fine too.

At last the vent ducting was visually checked from the outside of the building, and it was clean with no dust accumulated inside the ducting and no other debris. 

Problem solved; the customer was happy.

A piece of advice 

In fact, we found that customers often forgot to turn back on the valves to air headers after they were turned off, especially when the valves were within easy reach, and consequently they got weak suction at hoods. 

So, please check the openness of the valve to the air header of your pulse jet cleaning system before calling in a service contractor, as this will save your money and reduce your downtime.

Leak Test, Air Balancing, Trouble-shooting, and System Evaluation services by Airvate

  • Dye test for bag/cartridge leak 
  • Dust collection system and industrial ventilation system Testing and Air Balancing
  • Technical services: field survey and dust collection system audit / evaluation and trouble-shooting
  • New system start-up
  • Dust sample analysis
  • Dust collector selection and sizing: baghouse, wet scrubber, cyclone, settling chamber, drop-out box, etc.



Comments

Popular posts from this blog

What you have to know when applying blast gate damper

  Introduction A damper is a device that adjusts the volume of airflow passing through the outlet, inlet or duct. By proper adjustment of all dampers in a system, a desired distribution of airflows in all the branches can be obtained, while minimizing the total airflow of the system to save energy— this is also termed air balancing. The most common dampers used in industrial ventilation and dust collection systems to balance airflows are slide gate dampers (The slide gate, also called “blast gate or cut-off” damper). In a slide gate damper (see Figure 1 of a straight flat slide gate damper), the slide is inserted perpendicular to the flow. Figure 1 A sample of straight flat slide gate damper As the gate is sliding into the duct, it will add resistance to the airflow and consequently reduce the volume of airflow, while increasing airflows in all other branches. Withdrawing the gate has the reverse effect on that branch and all the others in a system. Interaction between a fan ...

Push-pull ventilation system for open surface tank saves air flow

  Three sections in this blog: Push-pull ventilation system and its advantages Disadvantages of general ventilation and side exhaust systems Methods to design a push-pull ventilation system Push-pull ventilation system and its advantages Open surface tanks used in industrial processes often need ventilating to remove harmful pollutants (vapors, fumes or aerosols) from the working environment. One method of removing pollutants is the so-called side push-pull ventilation system, in which a jet of air is blown (or pushed) from one side of the tank and collected (or pulled) by an exhaust hood on the opposite parallel side. This system is particularly useful for large tanks where access requirements preclude the use of an overhead canopy, and the size of the tank makes side (or rim) exhaust systems prohibitively expensive. Most agree that a push-pull ventilation system can yield air savings of up to 50% compared to a side suction only hood. An illustration of a push-pull system for an o...

Baghouse Dye Test for leak detection

  We did a Dye test for a customer in a newly installed baghouse. In this standard dye test procedure, green fluorescent dye powder was applied. No leaks were found in the clean plenum of the baghouse. All the bags were properly installed and no breach between the clean air and dirty air plenums was found either. View of Clean Plenum after Dye applied Per the request of our customer, we also got inside the dirty side of the baghouse through the inspection door on the hopper and visually checked dye powder distribution on the bags. From the picture below, it is apparent that the dye powder evenly distributed on all the bags, which means that the airflow was evenly distributed too. Customer was very happy about this visual check. Bottom View of Bags after Dye Applied