Industrial Manuals, Standards and Codes I’ve Consulted

 


When doing calculations, designing, and/or on-site work, we have to figure out which standard and code (federal, state, local) we will follow.  

EPA and Permits

On-site Measurement

Airborne Contaminants

Industrial Ventilation

  • Industrial Ventilation Manual by ACGIH (for Design and Operation & Maintenance)
  • OSHA Technical Manual (OTM) Section III, Chapter 3: Ventilation Investigation
  • ANSI/AIHA Z9, Ventilation Standards
  • SMACNA (The Sheet Metal and Air Conditioning Contractors' National Association)
  • NEBB: Procedural Standards or Guides for Air Balancing

Equipment Testing

  • ANSI/ASHRAE Standard 199: testing process to test how well dust collectors perform in real-world conditions

Pressure Vessel / Pressure Piping

  • ASME pressure vessel code
  • ASME B31.1: Power piping
  • ASME B31.3: Process Piping
  • ASME B16.5 Pipe Flanges & Flanged Fittings

FRP (Fiberglass Reinforced Polymer)

  • ASME RTP-1

Plastics

  • ISO 15494: Plastics Piping Systems for Industrial Applications (PB, PE, PE-RT, PE-X, PP)

Demolition

  • 29 CFR 1926.850(a) and OSHA Technical Manual (OTM) Section V: Chapter 1, Demolition

Others

  • OSHA and NIOSH: Small Business Safety and Health Handbook
  • The FDA Food Safety Modernization Act (FSMA)
  • ASCE 7: Minimum Design Loads for Buildings and Other Structures

Fire and Explosion Protection

  • FM Global Property Loss Prevention Data Sheets – 7-73 (Dust Collectors and Collecting Systems) & 7-76 (Prevention and Mitigation of Combustible Dust Explosion and Fire)
  • OSHA Technical Manual – Section IV, Chapter 6, Combustible Dusts
  • NFPA codes
    • NFPA 1: Fire Code
    • NFPA 13: Standard for the Installation of Sprinkler Systems
    • NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
    • NFPA 36: Standard for Solvent Extraction Plants
    • NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work
    • NFPA 61: Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities
    • NFPA 68: Standard on Explosion Protection by Deflagration Venting
    • NFPA 69: Standard on Explosion Prevention Systems
    • NFPA 70: National Electrical Code (NEC)
    • NFPA 77: Recommended Practice on Static Electricity
    • NFPA 85: Boiler and Combustion Systems Hazards Code
    • NFPA 86: Standard for Ovens and Furnaces
    • NFPA 90A: Standard for the Installation of Air-Conditioning and Ventilating Systems
    • NFPA 91: Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Particulate Solids
    • NFPA 92: Standard for Smoke Control Systems
    • NFPA 221: Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier Walls
    • NFPA 484: Standard for Combustible Metals
    • NFPA 651: Standard for the Machining and Finishing of Aluminum and the Production and Handling of Aluminum Powders
    • NFPA 652 for DHA (Dust Hazards Analysis)
    • NFPA 654: Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids
    • NFPA 664: Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities
    • NFPA 1192: Standard on Recreational Vehicles

Comments

Popular posts from this blog

Dust clogged up a baghouse

  We were called in by a customer on one cold morning. Their dust collection system did not work when they turned on power as usual. First, we checked the ductwork to see if there was any dust accumulated inside from the sucking points, to the fan, then to the baghouse. It seemed the ductwork was not the problem. After being in the baghouse, the filtered air went back to the workshop. Then we opened the access door of the baghouse hopper, and what we saw showed us the problem: it was packed with wood dust (Figure 1).  Figure 1 baghouse hopper packed with wood dust  Later, the access door on the clean side of the baghouse was opened, and one bag was taken out, it was very clear that the dust even accumulated between bags (Figure 2). Figure 2 dust clogged up between bags After the dust was removed from the baghouse, the system was turned on. In the first 20 minutes, the baghouse was warmed up without dust loading.  When this happened, the daytime temperature outdoors w...

Baghouse dye test for leak detection - 2

  In a periodic test of a baghouse dust collection system, dye test for leak detection was done to the baghouse by following the test procedure. The system collects wood dust, and the bags were installed 4 years ago. The air after the baghouse is recirculated back to the workshop to save energy, especially in winter. The dye test easily found glowing spots on some bags adjacent to the tubesheet with the help of a black light wand (Figure 1&2) . These spots were thought to be caused by the bleed-through of the green dye powder; they were not indicators of broken bags.  We put the dye test results in the comprehensive report for this periodic system test and explained our concerns to the customer.  Figure 1 Glowing spots under black light on bags, image 1 Figure 2 Glowing spots under black light, image 2 Leak Test, Air Balancing, Trouble-shooting, and System Evaluation services by Airvate Dye test for bag/cartridge leak  Dust collection system and industrial ventil...

Troubleshooting: Air Header got no air for the pulse jet cleaning system

  One customer told us that their dust collection system had a very weak suction on the grinding process line, and we went to their workshop on-schedule to do troubleshooting.  Introduction of the dust collection system The dusty air from the plastic grinder first ran through a cyclone and the separated dust from the cyclone directly went back to the process; the airflow with fine particles from the cyclone went to a cartridge dust collector, and then the filtered air was released to outside of the building. Since the plastic dust is combustible, an explosion panel and a vent duct were installed on the dust collector, and a non-return valve on the ductwork just in front of the dust collector inlet. The cartridge dust collector was equipped with a pulse jet cleaning system controlled by a Photohelic pressure gauge. The Photohelic Gauge measures the Differential Pressure and provides the capability for “on-demand” cleaning in conjunction with a Timer Board. Troubleshooting proce...